3A3PT60060–600 kVA
ARRAY 3A3 PT Modular UPS (60–600 kVA)
Enterprise modular UPS built on 60 kW hot-swappable power modules — up to 99% ESS efficiency and 8-unit parallel for hyperscale and colo data centers.
Power Rating
60–600 kVA
Topology
Modular, double conversion
Efficiency
up to 97% (online) / 99% (ESS)
Input
380/400/415 VAC
Output
380/400/415 VAC
Parallel
up to 8 units
Backup
external battery, configurable
Full Specifications
Overview
Series
ARRAY 3A3 PT (60–600 kVA)
Power Modules
60 kW per module (62.5 kW optional), hot-swappable
Frame Options
600 kW frame with standard input/output/MBS/bypass switches
Topology
Modular online double conversion
Standards
IEC 62040-1 / -2 / -3, RoHS
Input
Rated Input Voltage
380/400/415 VAC
Voltage Range
301–478 VAC (L-L); 175–276 VAC (L-N)
Frequency Range
50/60 Hz
Input Power Factor
> 0.99
Input Current Distortion
< 3% @ 100% load
Output
Rated Output Voltage
380/400/415 VAC, 4-wire
Voltage Regulation
±1% steady state
Voltage THD
< 1% (100% linear load); < 5% (non-linear load)
Overload Capability
125% for 10 min
Efficiency (Double Conversion)
Up to 97%
Efficiency (Energy Saver)
Up to 99%
Parallel Capability
4 units standard; up to 8 units with factory customization
Cold Start
Supported
Soft Start
Rectifier ramp-up, generator compatible, configurable ramp rate
Battery
Battery Type
Lithium or VRLA
Battery Voltage
432–528 VDC (selectable)
Battery Connection
Two-wire (no neutral)
Charging Method
ABM intelligent charging
Environment
Operating Temperature
0–40 °C
Noise
Low-noise design for white-space deployment
Specifications are subject to change without notice due to continuous product improvement. Confirm final parameters with our sales team for your order.